When fitting a flue system, building regulations specify clearances to
combustible materials depending on the type of flue pipe. These
clearances must be met to ensure legality and safety.
Single Wall Flue Pipe
Single
wall flue pipe (also referred to as vitreous enamel flue pipe) must be a
minimum of three times the diameter of the pipe away from a combustible
material.
Twin Wall Flue Pipe
Twin wall
flue pipe's clearance to combustibles is based on manufacturer
guidelines and so can differ between ranges. One factor is the thickness
of the insulation, which reduces the external temperature. Our range of
Bofill twin wall flue has 30mm thick insulation and has a 50mm clearance to combustibles.
If
the twin wall flue system is to run internally through the property and
runs through spaces where accidental human contact could occur (e.g. a
bedroom - not including the room where the appliance is located), the
flue must be boxed in. If the flue passes through a storage space such
as a cupboard or loft space, a guard must be placed no closer than 50mm
around the flue pipe.
Heat Shielding
Combustible
materials, such as a wall or ceiling, can be heat shielded using a
fireproof board. However there must be a 12mm air gap between the heat
shield and combustible material. The flue pipe must be at least 1.5
times its diameter away from the heat shield. The heat shield must
extend at least 1.5 times the diameter of the flue pipe beyond each side
of the flue pipe.
However always remember that fitting should only be carried out by a HETAS registered installer.
No comments:
Post a Comment